Air Circuit Breaker EPL-20 3H BF/M2C2S2/PR-LP 004695721
Specifications
- ETI Code:
- 004695721
- Description:
- EPL-20 3H BF/M2C2S2/PR-LP
- Class name:
- Air Circuit Breaker
- Rated current (A):
- 2000
- Number of poles:
- 3
- Rated impulse withstand voltage Uimp (kV):
- 8
- Catalogue Group:
- ETIPOWER
- Rated short-circuit breaking capacity at 415V Icu/Ics (kA):
- 85
- Rated operational voltage AC (V):
- 690
- Thermal adjustment:
- 0,4-1 xIn
- Magnetic adjustment:
- 1-15 xIn
- Adjustable or fixed:
- adjustable
- Connection type:
- rear connection
- Standards:
- 60947-2
Documents
Logistic Data
Product
- Net weight of the product
- 45.93 kg
- Customs tariff
- 85362090
Basic packaging
- Basic packaging quantity
- 1
- EAN code for a basic packaging
- 3838400106087
- Basic packaging weight
- 46.43 kg
Transport packaging
- Transport packaging quantity
- 6
- EAN code for a transport packaging
- 3838400106100
- Transport packaging weight
- 314 kg
- Pallet quantity
- 6
Intermediate packaging
- qty
- 1 pcs
- Weight
- 50.925 kg
- Height (mm)
- 600 mm
- Depth (mm)
- 600 mm
- volume
- 252 dm3
ETIM Clasification
- Classification
- EC000228
- Class name
- Power circuit-breaker for trafo/generator/installation protection
- Rated permanent current Iu
- 2000
- Rated voltage
- 690…690
- Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
- 85
- Integrated earth fault protection
- Yes
- Type of electrical connection of main circuit
- Rail connection
- Device construction
- Built-in device fixed built-in technique
- Suitable for DIN rail (top hat rail) mounting
- No
- DIN rail (top hat rail) mounting optional
- No
- Number of auxiliary contacts as change-over contact
- 5
- With switched-off indicator
- Yes
- With under voltage release
- No
- Number of poles
- 3
- Position of connection for main current circuit
- Back side
- Type of control element
- Push button
- Complete device with protection unit
- Yes
- Motor drive integrated
- Yes
- Motor drive optional
- Yes
- Degree of protection (IP)
- IP20