Air Circuit Breaker EPL-25 4H BD/M2C2S2/PR-LP 004695714

Specifications

ETI Code:
004695714
Description:
EPL-25 4H BD/M2C2S2/PR-LP
Class name:
Air Circuit Breaker
Rated current (A):
2500
Number of poles:
4
Rated impulse withstand voltage Uimp (kV):
8
Catalogue Group:
ETIPOWER
Rated short-circuit breaking capacity at 415V Icu/Ics (kA):
85
Rated operational voltage AC (V):
690
Thermal adjustment:
0,4-1 xIn
Magnetic adjustment:
1-15 xIn
Adjustable or fixed:
adjustable
Connection type:
rear connection
Standards:
60947-2

Documents

Product

Net weight of the product
104.93  kg
Customs tariff
85362090  

Basic packaging

Basic packaging quantity
1  
EAN code for a basic packaging
3838400105868  
Basic packaging weight
105.43  kg

Transport packaging

Transport packaging quantity
6  
EAN code for a transport packaging
3838400105882  
Transport packaging weight
688  kg
Pallet quantity
6  

Intermediate packaging

qty
1  pcs
Weight
112.425  kg
Height (mm)
650  mm
Depth (mm)
620  mm
volume
423.15  dm3
Classification
EC000228
Class name
Power circuit-breaker for trafo/generator/installation protection
Rated permanent current Iu
2500
Rated voltage
690…690
Yes
Number of auxiliary contacts as change-over contact
5
Number of poles
4
Degree of protection (IP)
EV006405
ETIM Classification – Version 7.0